138 Extreme Networks Consolidated Hardware Guide
Alpine 3800 Series Switch Chassis
Figure 62: The Alpine 3802 chassis requires 4 screws to be securely mounted in a rack
Grounding the Alpine 3800 Series Chassis
To ground your Alpine 3800 series chassis in accordance with NEBS standards, gather these materials:
Two zinc-plated steel lockwashers
Two zinc-plated steel nuts
One Panduit-style, standard two-hole barrel, copper compression lug
AWG, high strand-count copper wire cable, appropriate for your chassis
8 AWG for the Alpine 3808
10 AWG for the Alpine 3804
14 AWG for the Alpine 3802
To ground the chassis:
1 Strip 0.5 inch (1.2 cm) of insulation from the appropriate AWG, high strand-count copper wire cable.
2 Insert the cable into the cable lug.
CAUTION
Ensure that no copper is visible between the lug and the cable insulation.
3 Tighten the cable retention screw, using a
1
/
4
or
5
/
16
flathead screwdriver, to 20 in-lbs of torque.
4 Attach the ground lug, lock washers, and nuts (in that order) to the grounding studs on the rear of
the chassis. Tighten the nuts to 125 in-lbs of torque.
Removing the Chassis
This section describes how to remove the Alpine 3800 series chassis from a rack.
To uninstall the Alpine 3800 series chassis from a rack, you need the following tools, equipment, and